Wednesday, July 30, 2014

Preventive Maintenance test with Insulation Resistance Test, Part 2

Part 1 covers the introduction of the insulation resistance test in preventive maintenance can be found here.
What are the test methods for insulation resistance test?
There are three types of tests for measuring insulation resistance.
  • Spot reading
  • Time-resistance
  • Step voltage
Each test applies its own methodology that focuses on a specific insulating property of the devices being tested. Users need to choose the one that best fits the test requirements.

Spot test
A test voltage is applied for a short interval until a stable reading is achieved, or for a fixed period of time, normally 60 seconds or less. The reading is collected at the end of the test. This test is normally performed for Go/NoGo testing or historical records. Temperature and humidity variations may affect the readings and have to be compensated for if necessary.

For the historical record, a curve is plotted based on the history of the readings. Observation of the trend is taken over a period of time, normally over years or months. 
Figure 3 For an effective monitoring the equipment insulation resistance, the insulation resistance values collected at each test interval should be plotted at the graph to track it’s trend


This test is suitable for a device with a small or negligible capacitance effect, e.g. short wiring run.


Time-resistance test
Successive readings are taken at a specific time, typically every few minutes, and difference in readings compared. Good insulation will show a continual increase in the resistance value. If the reading is stagnant and it does not increase as expected, the insulation may be weak and attention may be needed. Moist and contaminated insulation may lower resistance readings since they will increase the leakage current during testing. The temperature influence on this test is negligible as long as there is no significant temperature change in the device under test.
This test is suitable for the predictive and preventive maintenance of rotating machines.
The polarization index (PI) and dielectric absorption ratio (DAR) are commonly used to quantify the time-resistance test result.
Figure 2 Curve plot of a time-resistance test made on a motor winding with Keysight Handheld Meter Logger software. Good insulation shows a continual increase in resistance, the trend line should be in inverse exponential


The polarization index is defined as the ratio of the 10 minute resistance value to the 1 minute resistance value. The interpretation of the value is shown in Table 1. The IEEE Std 43-2000 recommends the minimum value of PI for AC and DC rotating machinery in thermal class B, F and H as 2.0, and the minimum PI value for class A equipment is 1.5.
NOTE: Some new insulation systems have a faster response to the insulation test. They usually start with test result at GΩ range yielding a PI between 1 and 2. In these cases, the PI calculation may be disregard. According to the IEEE Std 43-2000, if the 1 minute insulation resistance is above 5 GΩ, the calculated PI may not be meaningful.
Dielectric absorption ratio is referred to the ratio of the 60 second resistance value to the 30 second resistance value. The interpretation of the value is shown in Table 1.
DAR is suitable for devices with insulation materials in which the absorption current decreases quickly.

Table 1. PI and DAR test result interpretation

Insulation condition
PI value
DAR value
Insufficient
< 2
< 1.25
OK
2 to 4
< 1.6
Excellent
> 4
> 1.6


Different voltage levels are applied in steps to the device under test. The recommended ratio of the test voltage is 1:5. The test at each step is same length, usually 60 seconds, and goes from low to high. This test is normally used at test voltages lower than the rated voltage of the equipment. The rapid increase of the test voltage level creates additional stress on the insulation and causes the weak point to fail, subsequently leading to a lower resistance value.
This test is particularly useful when the rated voltage of the equipment is higher than the available test voltage generated by the insulation resistance tester.



In the last article (Part 3), I will cover the test voltage selection, minimum insulation resistance, as well as the safety consideration for the insulation resistance test.

Thursday, July 24, 2014

Preventive Maintenance test with Insulation Resistance Test, Part 1


Preventive maintenance is a predetermined task performed based on a schedule and its objective is to keep equipment in good condition to avoid breakdowns.
Insulation resistance testing is commonly performed as part of electrical testing in a preventive maintenance program for rotating machines, cables, switches, transformers, and electrical machinery where insulating integrity is needed. Insulation resistance testing in the preventive maintenance program helps identify potential electrical issues to reduce unpredictable, premature equipment repair and replacement cost.


With properly scheduled monitoring and data collection, this testing can be very useful in analyzing and predicting the current and future behavior of equipment. Early problem detection helps avoid major repairs, resulting in cost savings when compared to a run-to-failure maintenance practice. Preventive maintenance has the added benefit of pre-planning for necessary parts and resources.

This first of three articles will describe what is insulation resistance testing, how it plays a part in preventive maintenance and factors that affect insulation resistance. The second article will focus on the methods of insulation resistance testing1  while the last article will detail test voltage selection guidelines and safety considerations.

1 Consulting the original product/equipment manufacturer for more detailed information is recommended.
 

What is Insulation Resistance Testing?
Insulation resistance is used to verify the integrity of the insulation material. It can be the cable insulation or motor/generator winding insulation. Insulation resistance testing is carried out by applying a constant voltage to the equipment under test while measuring the any flowing current. High DC voltages are used causing a small current to flow through the insulator surface. The total current consists of three components: capacitance charging current, absorption current, and leakage current (refer to Figure 1.)


  • Capacitance charging current is relatively high upon start-up and drop exponentially within a few seconds to a few ten seconds. It is normally negligible when the reading is taken.
  • Absorption current decays at a decreasing rate. It may require up to a few minutes to reach zero depending on the insulation materials.
  • Leakage current is constant over time.
Figure 1 Components of test current
How Insulation Resistance Testing Helps in Preventive Maintenance
For an effective test, results should be regularly recorded over a period of time and compared with earlier recorded values taken when the equipment was new and in good condition. The trend of the readings over a period of time will help identify the presence of anomalies. Insulation resistance values that are consistent over time indicate that the equipment’s insulation properties are good. If the resistance values are decreasing, it indicates that potential issues can occur sometime in the future and more thorough preventive maintenance should be scheduled soon.

Factors That Affect the Insulation Resistance
The factors that commonly affect the insulation resistance are:
  • Surface condition. For example oil or carbon dust on the equipment’s surface that can lower the insulation resistance.
  • Moisture. If the equipment’s surface temperature is at, or below, the dew point of the ambient air, a film of moisture forms on its surface would, lowering the equipment’s resistance value.
  • Temperature. The insulation resistance value may vary inversely with the change of the temperature. Its influence on readings can be mitigated by performing preventive maintenance testing at the same temperature each time. If the temperature cannot be controlled, normalizing to a base temperature such as 40 °C is recommended. This is commonly done using the estimation rule, “Every 10 °C increase in temperature halves the insulation resistance, while a 10 °C reduction doubles the resistance”.  As different materials may have different degrees of resistance change due to temperature, for more precise temperature correction, some may adopt a temperature correction factor the measurement reading should be multiplied by multiplying the measurement reading with the temperature correction factor at the corresponding temperature.

In the next article (Part 2), I will cover the insulation resistance test methods.